4-1

Setting up inverter

Step 1
Step 2
Step 3
Table 14 Extended Speed I/O Output Words
Word
Bit Allocation
7
6
5
4
15
14
13
12
Instance ID 21: Extended Speed Control Output
n
-
REF CTR
-
-
-
-
-
n + 1
Rotational Speed Reference (default [0.01 Hz])
Rotational Speed Reference
Table 15 Extended Speed I/O Input Words
Word
Bit Allocation
7
6
5
4
15
14
13
12
Instance ID 71: Extended Speed Control Input
n
ARF RFN CFN RDY DRR DFR WR FLT
Drive Status (see below)
n + 1
Rotational Speed Monitor (default [0.01 Hz])
Rotational Speed Monitor
!Caution
This section provides some common usage examples to help you get started.
Unless otherwise specified, all usage examples make use of the Extended
Speed IO format as the default connection path (Refer to section 3-1 Installa-
tion of EDS files, Step 2). Prepare the Inverter and Option Board before start-
ing with the usage examples:
Initialize the Inverter mode to Std. IM by first setting b171 = 1 and then
b180 = 1 (Refer to MX2 User's manual (Cat. No. I570) section 3-6-24).
Set the Inverter rating to CT (constant torque) by setting b049 = 0 (Refer to
the MX2 User's manual section 3-2-5).
Configure the Option Board and Network as explained in sections 3-1 Installa-
tion of EDS files and 3-2 Configuring the Option Board with Extended Speed
IO (Output assembly 21, Input assembly 71). There are two options:
• When using Fixed allocation method of configuring the master, select
P046 = 1.
• When using User-set allocation, select the two Extended Speed IO
assemblies.
If you configured everything correctly, your output and input I/O words should
contain the following data:
Bit
3
2
1
0
FWD Forward/Stop
11
10
9
8
REV
RST
-
RST REV FWD
-
-
-
-
CTR
REF
Bit
3
2
1
0
FLT
11
10
9
8
WR
DFR
DRR During reverse run 0: Stop/forward
RDY
CFN
RFN
ARF
Check the Inverter settings for proper Inverter behaviour before actually oper-
ating the Inverter remotely via the network.

Operations and Monitoring

Name
Description
0: Stop
1: Forward
Reverse/Stop
0: Stop
1: Reverse
Fault Reset
Reset Fault/Trip condition on transi-
tion from 0 to 1
NetCtrl
Run command selection.
0: Setting of A002
1: Network controlled
NetRef
Speed reference selection.
0: Setting of A001
1: Network controlled
Name
Description
Fault
0: Normal
1: Fault/Trip
Warning
0: Normal
1: Warning
During forward run 0: Stop/reverse
1: During forward run
1: During reverse run
Inverter ready
0: Inverter not ready
1: Inverter ready
Ctrl from Net
Run command input selection
0: Local
1: DeviceNet reference
Ref from Net
Speed reference input selection
0: Local
1: DeviceNet reference
At reference
0: Accel/decel phase
1: At reference
SECTION 4
Drive Status
Value Description
1
Startup
2
Not ready
3
Ready
4
Enabled
5
Stopping
6
Fault/Trip Stop
7
Faulted/Tripped
21