Controlling Inverter Torque
Step 1
Step 2
Step 3
Step 4
Step 5
Table 16 Extended Speed Torque I/O Output Words
Word
Bit Allocation
7
6
5
4
15
14
13
12
Instance ID 123:
Extended Speed and Torque Control Output
n
-
CI7 CTR CI5
CO2 CO1 CR
-
n + 1
Rotational Speed Reference (default [0.01 Hz])
Rotational Speed Reference
n + 2
Torque Reference [1 %]
Torque Reference
n + 3
Torque Compensation Bias [1 %]
Torque Compensation Bias
Table 17 Extended Speed Torque I/O Input Words
Word
Bit Allocation
7
6
5
4
15
14
13
12
Instance ID 71: Extended Speed Control Input
n
FLT WR RDY ARF
-
-
MO2 MO1 MR CFN
n + 1
Rotational Speed Monitor (default [0.01 Hz])
Rotational Speed Monitor
n + 2
Torque actual [1 %]
Torque actual
n + 3
Output current monitor [0.1 A]
Output current monitor
n + 4
-
MI7 MI6 MI5 MI4 MI3 MI2 MI1
-
-
-
-
Step 6
24
Configure the Option Board and Network as explained in sections 3-1 Installa-
tion of EDS files and 3-2 Configuring the Option Board with Control IO and
Multi function IO monitor (Output assembly 101, Input assembly 151). There
are two options:
• When using Fixed allocation method of configuring the master, select
P046 = 4.
• When using User-set allocation, select the two Extended Control IO and
Multi-function IO monitor assemblies.
Set C003 = 52 (ATR: permission of torque command input) to assign intelli-
gent input terminal 3 as torque enable. See also section 4-3 Overriding
Inverter inputs
Set parameter A044=3 to enable Sensorless Vector Control (SLV).
Set parameter P033=6 to assign Torque command input selection to Option
Board.
Restart the Inverter or reset the Option Board for the new settings to take
effect.
Note
The Inverter will only allow setting of torque related registers if it is configured
to operate with CT rating in Std. IM mode.
Your input and output process areas should now have the following layout:
Bit
3
2
1
0
FWD Forward/Stop
11
10
9
8
REV
RST
CI4
CI3 REV FWD
FFL
-
-
RST FFL
CI3 to
CI7
CO1,
CO2,
CR
Bit
3
2
1
0
DFR
11
10
9
8
DZS
DRR During reverse run 0: Stop/forward
-
DRR DZS DFR
-
-
ARF
RDY
WR
FLT
CFN
-
-
-
-
MO1,
MO2,
MR
Set the maximum allowable output frequency in torque mode by configuring
P039 and P040 for the forward- and reverse run directions. Be careful to
select safe limits for your test setup.
Name
Description
0: Stop
1: Forward
Reverse/Stop
0: Stop
1: Reverse
Fault Reset
Reset Fault/Trip condition on transi-
tion from 0 to 1
Force Fault
Force external fault/trip from network
Control/Override
0: Reset 1: Set override for Multi
Input
Function input 3 to 7.
Set (Relay) Output 0: Reset 1: Set Multi Function 1 to 2
or Relay Output (CR).
Name
Description
During forward run 0: Stop/reverse
1: During forward run
During zero speed 0: Non-zero speed
1: During zero speed
1: During reverse run
At reference
0: Accel/decel phase
1: At reference
Inverter ready
0: Inverter not ready
1: Inverter ready
Warning
0: Normal
1: Warning
Fault
0: Normal
1: Fault/Trip
Control from net
Run command input selection
(0: local, 1: DeviceNet)
Monitor (Relay)
0: OFF
outputs
1: ON
Section 4-4