Extended Data 2 I/O Mapping

C-3
Extended Data 2 I/O Mapping
C-4

Operation Command and Inverter Status Registers

Table C-4 Conventional control status regs
Bit
Operation Command
Name
0
Forward Run/Stop
(FW)
1
Reverse Run/Stop
(RV)
2
Intelligent Input
Terminal override [3]
3
Intelligent Input
Terminal override [4]
4
Intelligent Input
Terminal override [5]
5
Intelligent Input
Terminal override [6]
6
Intelligent Input
Terminal override [7]
7
(Reserved)
8
External Trip (EXT)
9
Trip Reset (RS)
10
(Reserved)
11
(Reserved)
12
(Reserved)
13
(Reserved)
62
Note
The Torque Compensation only becomes effective if: P036 = 5, A044 = 3 and
ATR is assigned to a digital input and turned on (Refer to MX2 User Manual
section 3-9-4)
Note
The Analog Output Channel 1 only becomes effective if: C028 = 16 (Refer to
MX2 User Manual section 3-7)
Note
A Digital Output only becomes effective if the associated register (C021, C022
or C026) is set to 63 (Refer to MX2 User Manual section 3-7)
Table C-3 Ext2 data format I/O mapping
Word Offset
+0
Operation Command
(Section C-4)
+1
Frequency Reference
+2
Modbus
Message Area
+3
(Section C-5)
+4
+5
*1.
Refer to section C-4 Operation Command and Inverter Status Registers on page 62 for the Op-
eration Command and Inverter Status register definitions
Description
1: Run forward
0: Stop run forward
1: Run reverse
0: Stop run reverse
1: ON
0: OFF
1: ON
0: OFF
1: ON
0: OFF
1: ON
0: OFF
1: ON
0: OFF
0➞1: Trip inverter
1: ON
0: OFF
-
-
-
-
Output Area
*1
Inverter Status
Output Frequency
Instruction
Modbus
Message Area
(Section C-5)
Data
Control
Inverter Status
Name
Operation Status
0 Hz Detection
Signal (ZS)
Rotation Direction
Trip Reset Status
Set Frequency
Reached (FA3)
Inverter Ready
Alarm Signal (AL)
Trip Status
(Reserved)
(Reserved)
PROFIBUS Control
Status
Alarm Relay Output
Terminal Status
Intelligent Output
Terminal [11]
Intelligent Output
Terminal [12]
APPENDIX C
Input Area
*1
(Section C-4)
Result
Data
Status
Description
1: Inverter is running
0: Inverter is stopped
1: ON
0: OFF
1: Reverse rotation
0: Forward rotation
1: Trip reset (RS) is active
0: Trip reset (RS) not active
1: ON
0: OFF
1: ON
0: OFF
1: ON
0: OFF
1: Inverter is tripped
0: Inverter not tripped
Always 0
Always 0
1: PROFIBUS is control source
0: PROFIBUS not control source
1: ON
0: OFF
1: ON
0: OFF
1: ON
0: OFF