Configuring the Option Board
Step 4
Step 5
Step 6
14
Table 8 Configuration of PROFIBUS parameters (continued)
Param
Description
P045
Action on Network
Error
P181
Output Data Keep
Mode
Registers A001 and A002 are used by the Inverter to adjust the frequency
source and control source. If the second motor parameter set is used, regis-
ters A201 and A202 also have to be set. Adjust these in accordance with the
following table:
Table 9 Configuration of Inverter source selection parameters
Param
Description
A001
Motor 1
Frequency Source
A201
Motor 2
Frequency Source
A002
Motor 1 Run
Command Source
A202
Motor 2 Run
Command Source
Registers P033, P036, C021, C022 and C028 are used by the Inverter to
adjust some Inverter function sources. If required (refer to usage examples),
adjust these in accordance with the following table:
Table 10 Configuration of Inverter function source parameters
Param
Description
P033
Torque Command
Source
P036
Torque Bias Mode
C021
Output Terminal 11
Source
C022
Output Terminal 12
Source
C026
Alarm Relay Output
Terminal Source
C028
Analog Output AM
Source
The PPO modules and Flexible module give you the freedom to select/cust-
omise the Inverter Modbus registers for Cyclic Data Exchange. Inverter regis-
ters P160 - P179 are used to configure and map the exchanged Modbus
registers. If required, adjust these registers to change the default content of
the exchanged data. Please refer to Appendices B-1 I/O Mapping on page 58
and D-1 Flexible I/O Mapping on page 66 for more details.
Setting
Set to 0 for inverter trip
Set to 1 for deceleration and trip
Set to 2 for no action
Set to 3 for stop due to free-run
Set to 4 for deceleration and stop
Define behaviour if PROFIBUS master indicates
CLEAR mode or if a network error occurs:
Set to 0 for clearing all output data (stop inverter)
Set to 1 for keeping output data (inverter continues
operating)
Setting
For option board as source:
Set to 3 if P182 equals 2
Set to 4 if P182 equals 0 or 1
Setting
For option board as source:
Set to 6 (Use Option Board register) if P182
equals 1
Set to 3 (Use P034) if P182 equals 0 or 2
For option board as source:
Set to 5 (Bias set by Option Board) if P182
equals 1
Set to 0 (Bias according to sign) or 1 (Bias accord-
ing to rotation direction) if P182 equals 0 or 2
Set to 63 for option board as source
Set to 63 for option board as source
Set to 63 for option board as source (Optional)
Set to 16 for option board as source