Accessing Parameters
Step 3
Step 4
!Caution
4-5-2
PROFIdrive DP-V1 Parameter Channel
Table 48 Parameter Processing Message Area-Changing A001
Output area [hex] 7
Word offset
Function
Input area [hex]
Reading an Inverter parameter (DWORD): To read Inverter parameter F002
(Acceleration time 1):
Table 49 Parameter Processing Message Area-Reading F002
Output area [hex] 6
Word offset
Function
Input area [hex]
Read value: Acceleration time = 000003E8h = 1000 = 10.00 sec
Changing an Inverter parameter (DWORD): To change Inverter parameter
F002 (Acceleration time 1) to 3.00 sec:
Table 50 Parameter Processing Message Area-Changing F002
Output area [hex] 8
Word offset
Function
Input area [hex]
Do not access Inverter parameters while the Inverter is being re-initialized
(Refer to the MX2-A@ Inverter manual section 6-3). Accessing parameters
during a re-initialization will cause the Inverter to go into an undefined state.
3G3AX-MX2-PRT-E Option Board provides Parameter Access in accordance
with the PROFIdrive V4 profile definition. Access is only supported on DP-V1
Class 2 slot 0, index 47. You will therefore have to ensure that all
MSAC2_Initialize, MSAC2_Write, MSAC2_Read and MSAC2_Abort mes-
sages make use of slot 0, index 47.
Note
The OMRON web-site (http://industrial.omron.eu) provides function blocks
that automate parameter access when using the CJ1W-PRM21 / CS1W-
PRM21 version 3.0 or newer. These function blocks automate the DP-V1
Class 2 related commands to the PROFIBUS master as well as the DP-V1
parameter channel request and response formats. You can skip this section if
you are using these function blocks.
Change WORD element value in array task
Parameter number 1
Parameter group A
001
01
+0
+1
AK
PNU
IND
4
001
01
Task success (WORD element) response
Read element value in array task
Parameter number 2
Parameter group F
002
06
+0
+1
AK
PNU
IND
5
002
06
Task success (DWORD element) response
Write value: 3.00 sec = 300 = 0000012Ch
Change DWORD element value in array
Parameter number 2
Parameter group F@@@
002
06
+0
+1
AK
PNU
IND
5
002
06
Task success (DWORD element) response
Section 4-5
Write
00
0000
+2
-
PWE
00
0000
00
0000
+2
-
PWE
00
0000
00
0000
+2
-
PWE
00
0000
0003
+3
0000
0000
+3
03E8
012C
+3
0000
31