Configuring the Option Board

Step 1
Step 2
Step 3

Configuring Drive Parameters and Option Board

All Option Board parameters are stored in the MX2-A@ Inverter. This allows
for easy replacement of the Option Board without the need to re-configure.
After connecting the Option Board to an MX2-A@ Inverter for the first time
however, proceed with the following steps:
The Option Board supports 3 device profiles. Each device profile supports a
subset of the modules listed in the GSD file. The device profile is selected
using Inverter parameter P182. Use the Inverter keypad to adjust P182 to
select the device profile and supported modules.
Table 6 Configuration of device profile
P182
Device Profile
0
PROFIdrive
(default)
[Appendix B]
1
Conventional
[Appendix C]
2
Flexible
It is recommended to set C102 = 3 to prevent the Inverter reset input and
Stop/reset button from interfering with Option Board during operation (Setting
C102 to another value causes the Option Board to reset when a trip condition
is cleared). Use the Inverter keypad to set C102 to 3.
Table 7 Configuration of Inverter Reset Mode Selection
Param
C102
Reset mode selection Recommended to set to 3 (Reset mode selection
Inverter registers P180, P044, P045 and P181 configure the PROFIBUS net-
work-related parameters. Adjust these to configure the node address, CLEAR
mode behaviour and required action when a Fieldbus failure occurs.
Table 8 Configuration of PROFIBUS parameters
Param
P180
PROFIBUS Node
Address
P044
Network Error Timer
PPO Type 1 (4 words PKW + 2 words PZD)
PPO Type 2 (4 words PKW + 6 words PZD)
PPO Type 3 (2 words PZD)
PPO Type 4 (6 words PZD)
PPO Type 5 (4 words PKW + 10 words PZD)
Basic Data
Extended Data 1
Extended Data 2
Flexible (10 words output and input)
[Appendix D]
Description
resets trip only, not Option Board)
Description
0 to 125, 0 (default) means node address 126
Time to wait after a network error occurs before
executing action in P045:
0 to 9999 in 0.1 s units
SECTION 3
Supported Modules
Setting
Setting
13