I/O Mapping - Omron 3G3AX-MX2-PRT-E User Manual

Mx2 profibus option board
Hide thumbs Also See for 3G3AX-MX2-PRT-E:
Table of Contents

Advertisement

I/O Mapping

B-1
I/O Mapping
Table B-1 PPO format I/O Mapping
Word Offset
PPO1
PPO2
PPO3
+0
+0
+1
+1
+2
+2
+3
+3
+4
+4
+0
+5
+5
+1
+6
+7
+8
+9
Note 1
Note 2
58
*1
PPO4
PPO5
+0
PKE
+1
IND
+2
PWE
+3
+0
+4
PZD1 Modbus register set by P160
+1
+5
PZD2 Modbus register set by P161
+2
+6
PZD3 Modbus register set by P162
+3
+7
PZD4 Modbus register set by P163
+4
+8
PZD5 Modbus register set by P164
+5
+9
PZD6 Modbus register set by P165
+10
PZD7 Modbus register set by P166
+11
PZD8 Modbus register set by P167
+12
PZD9 Modbus register set by P168
+13
PZD1
0
If no Word Offset is specified for a Register, the Register does not exist in the
Input and Output Areas for the Module Type
The Modbus addresses for the MX2-A@ Inverter are listed in section B-4-2 of
the MX2 user's manual.
P160-P169 can also be accessed as PNU915.1 - PNU915.10
P170-P179 can also be accessed as PNU916.1 - PNU916.10
Content
Output Area
Task ID and Parameter num-
ber
PNU index / Parameter
group in high byte
High word of value
Low word of value
or STW if P160 = 0
or HSW if P161 = 0
or ignored if P162 = 0
or ignored if P163 = 0
or ignored if P164 = 0
or ignored if P165 = 0
or ignored if P166 = 0
or ignored if P167 = 0
or ignored if P168 = 0
Modbus register set by P169
or ignored if P169 = 0
APPENDIX B
*2
Input Area
PKE
Task ID and Parameter num-
ber
IND
PNU index / Parameter
group in high byte
PWE
High word of value
Low word of value or Error
number
PZD1 Modbus register set by P170
or ZSW if P170 = 0
PZD2 Modbus register set by P171
or HIW if P171 = 0
PZD3 Modbus register set by P172
or always 0 if P172 = 0
PZD4 Modbus register set by P173
or always 0 if P173 = 0
PZD5 Modbus register set by P174
or always 0 if P174 = 0
PZD6 Modbus register set by P175
or always 0 if P175 = 0
PZD7 Modbus register set by P176
or always 0 if P176 = 0
PZD8 Modbus register set by P177
or always 0 if P177 = 0
PZD9 Modbus register set by P178
or always 0 if P178 = 0
PZD1
Modbus register set by P179
0
or always 0 if P179 = 0