Goodrive880 Series Water-Cooled Drive Hardware Manual
For water-cooled rectifier units
2.
To ensure that water-cooled rectifier units are installed reliably and in good heat dissipation, pay attention
to the following:
The unit must be installed and used in a cabinet.
A minimum ventilation clearance must be kept from the top and bottom of the rectifier unit to ensure
good heat dissipation. See Figure 3-7.
Figure 3-7 Installation space requirements for water-cooled rectifier units
Cabinet inlet and outlet area
3.
To ensure good heat dissipation of the inverter unit, design the air inlet and outlet as follows:
Air inlet area formula: S
S indicates the system ventilation area;
S
indicates the each module ventilation area with a unit of cm
module
Air outlet area formula: S
For details about the air volumes required by the units, see Table 3-1.
No.
1
2
3.3.5.2 Cabinet requirements
The cabinet frame must be strong enough to withstand the weight of components, control circuits and
1.
other equipments installed in it.
The cabinet must provide contact-proof shields for the powered circuits, and meet the requirements in
2.
terms of dust and humidity.
To facilitate installation, it is recommended to leave sufficient space around the device: space for
3.
cooling air flow, necessary clearance, and space required by the cable and cable support structure. Do
202212 (V1.0)
≥
≥
Front view
= (1.5~2.0) x (S
in
module1
= (1.2~1.5) x S
out
Table 3-1 Ventilation areas and actual air volumes of units
Frame size
DTLC
2A8LC
Violation of the requirements in section 3.3.5.1Installation space and heat
dissipation will shorten the inverter unit life and may result in inverter unit failure or
malfunction.
≥
Side view
+ S
+ S
+.........+ S
module2
module3
in.
Ventilation area S
(cm
in
416
832
Mechanical installation
≥
);
module N
.
2
)
Actual air volume (CFM)
2
460
920
25