Input power connection

Voltage (U
)
1
Short-circuit withstand
strength (IEC 60439-1)
Short-circuit current
protection (UL 508 C
CSA C22.2 No. 14-05)
Frequency
Imbalance
Fundamental power factor
(cos phi
)
1

Motor connection

Voltage (U
)
2
Frequency
Frequency resolution
Current
Power limit
Field weakening point
Switching frequency
Maximum recommended
motor cable length

Efficiency

208/220/230/240 V AC 3-phase ± 10% for 230 V AC units
380/400/415 V AC 3-phase ± 10% for 400 V AC units
380/400/415/440/460/480/500 V AC 3-phase ± 10% for 500 V AC units
525/550/575/600/660/690 V AC 3-phase ± 10% for 690 V AC units
Maximum allowable prospective short-circuit current is 65 kA when protected by fuses
given in the
IEC data
fuse tables.
US and Canada: The drive is suitable for use on a circuit capable of delivering not more
than 100 kA rms symmetrical amperes at the drive nominal voltage when protected by
fuses given in the
NEMA data
48 to 63 Hz, maximum rate of change 17%/s
Max. ± 3% of nominal phase to phase input voltage
0.98 (at nominal load)
0 to U
, 3-phase symmetrical, U
1
DTC mode: 0 to 3.2 · f
FWP
U
Nmains
f
=
· f
FWP
Nmotor
U
Nmotor
f
: frequency at field weakening point; U
FWP
U
: rated motor voltage; f
Nmotor
0.01 Hz
See section
IEC data.
1.5 · P
, 1.1 · P
or P
hd
N
cont.max
8 to 300 Hz
3 kHz (average). In 690 V units 2 kHz (average).
Sizing method
according to I
and I
2N
2hd
according to I
at
cont.max
ambient temperatures below
30 °C (86 °F)
according to I
at
cont.max
ambient temperatures above
30 °C (86 °F)
Note: With cables longer than 100 m (328 ft), the EMC Directive requirements may not be
fulfilled. See section
CE
marking.
Approximately 98% at nominal power level
fuse table.
at the field weakening point
max
. Maximum frequency 300 Hz.
: mains (input power) voltage;
Nmains
: rated motor frequency
Nmotor
(whichever value is greatest)
Max. motor cable length
DTC control
R2 to R3: 100 m (328 ft)
R4 to R6: 300 m (984 ft)
R2: 50 m (164 ft) Note: This applies to units with EMC filter
also.
R3 and R4: 100 m (328 ft)
R5 and R6: 150 m (492 ft)
Scalar control
R2: 150 m (492 ft)
R3 to R6: 300 m (984 ft)
Technical data
123