LUNA2000-200KWH-2H1 Smart String ESS
Maintenance Manual
Alarm
Alarm
ID
Name
3042
Rapid
Shutdown
Cable
Connectio
n of
Battery
Pack
Abnormal
Issue 02 (2023-02-28)
Severity
Possible Cause
Major
Cause ID = 1
The rapid shutdown
cabling between
battery racks is
incorrect.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Suggestion
If the system is in the array topology
identification process, wait until the
process is complete or exit the
process.
1. Locate the input and output
circuit breakers associated with
[ESC-No].
2. Issue a shutdown command, turn
off the switch on the battery side,
the switch on the bus side, and
the AC power supply switch, and
wait for 5 minutes.
3. Check whether the rapid
shutdown cables between battery
racks under [ESR-CabinetNo] are
correctly connected by referring
to the DCDC replacement section
in the maintenance manual of
the product.
4. Check that the cables are securely
connected. Turn on the AC power
supply switch, the switch on the
battery side, and the switch on
the bus side in sequence, and
issue a startup command.
5. If the alarm persists, contact your
dealer or technical support.
3 Alarm Reference