A. GENERAL
Installation of these power gas burners must conform to local codes, or in their absence, the National Fuel
Gas Code, ANSI Z223.1/NFPA 54.
In CANADA, "The equipment shall be installed in accordance with the Provincial Installation Requirements,
or in their absence, the CGA B149.1 and B149.2 Installation Codes shall prevail." Authorities having
jurisdiction should be consulted before installations are made.
ANSI or local installation code compliance is the sole responsibility of the qualified installer.
B. VENTILATION
The LC2300M burner models covered by this manual shall not be installed in an appliance located where
normal air circulation or infiltration is limited in providing all the air necessary for proper combustion and
draft hood dilution air.
When the heating appliance is installed in a tightly closed room without ventilation openings to outdoors, or
other rooms, provisions shall be made for supplying air for combustion through special openings, one near
the floor line and the other near the ceiling. Each is to be sized based on one square inch (645.2 mm
of free area each 1,000 BTU (0.29 kW) input per hour.
C. MOUNTING TO EQUIPMENT
Mount the burner to the intended application by using 4 bolts within the intended slots. If new mounting holes
are needed, use the flange mount (Figure 1 shown below) as a template.
NOTE: THE BURNER AIR TUBE MUST NOT BE ALLOWED TO EXTEND INTO THE
CHAMBER; IT MUST BE SET 1/8 INCH (3.2MM) SHORT OF THE INSIDE SURFACE.