Parameter Number
Fuel 0
Gas
041
042
50
113
197
198
63899-002 Rev. A 3/20/2024
TABLE 3: COMMON PARAMETERS
User = U
Parameter Name
Service = S
OEM = O
Service Level
O
Password
OEM Level
O
Password
Backup/Restore
S
Burner ID
U/S
LMV3
Flame Sensitivity
S/O
Flame Sensitivity
S/O
Switch Point
Factory
Range
Setting
Any 4
9876
characters
Any 5
EntrY
Characters
Backup-0
-99-50
Restore -0
0-
Not Set
99999999
1
0-1
4
2-9
Description
The service level password can be
changed here. It must be exactly 4
characters in length. Enter the same
password twice to change it (n = new,
r = repeat)
The OEM level password can be
changed here. It must be exactly 5
characters in length. Enter the same
password twice to change it (n = new,
r = repeat).
Used to perform parameter backups
and restores.
Backup: LMV3 transfer to AZL
Restore: AZL transfer to LMV3
Set parameter to 1 and press enter to
begin the backup or restore. When the
value changes back to 0, the backup
or restore was completed
successfully. If the value changes to
any other number besides 0, see error
code 137 for the cause of the failure.
Burner ID is set here. The burner ID
must be all digits (no letters), from 1-
8 digits in length. Typically, the
burner serial number is used. This
serves as an identifier for the
parameters set. The burner ID must
be set to perform any backup or
restore.
Sets the flame signal sensitivity
during phases 60-70 for ION (flame
rod) and UV flame detectors.
0 = standard sensitivity
1 = high sensitivity
Sets the switching point on the
fuel/air ratio curve for high flame
sensitivity.
2 = no switching point (always high
sensitivity)
3-9 = sets the points (P3-P9) to switch
back to standard sensitivity