15. Press simultaneously "F" and "+/-" to set the ignition position of the fuel actuator. Your screen will
appear as below. The dashes (- - -) to the right of the fuel value indicate that there is no value set for
the air actuator. The burner will fault if no value is set, even if the air actuator will remain at 0. To
input a position for the air actuator, simultaneously press "A" and "+/-" to set the ignition point.
16. Press "+" to proceed to the next curve point.
17. P9 will appear flashing. This is the setpoint for high fire. Using Table 1 above in SECTION I -
INSTALLATION on page 13, generic gas and air actuator settings are shown with their
corresponding BTU rate.
NOTE: THESE ARE NOT EXACT VALUES FOR EVERY APPLICATION. AIR AND GAS
SETTINGS MAY NEED MODIFIED AFTER INSTALLATION IN EVERY APPLICATION.
18. The same procedure as in Step 14 with setting the fuel and air actuator at P0 will be followed.
NOTE: IT IS IMPORTANT TO SET P0 AND P9 AS ACCURATELY AS POSSIBLE FOR EACH
APPLICATION. THESE SETTINGS ARE USED TO CALCULATE THE REMAINING
19. When P9 values are set, press "+" to start the burner.
20. Once P0 and P9 are set and the burner has been initiated, the burner motor will then start, and the
burner will cycle through the same set of phases as in SECTION II - INITIAL SET-UP.
63899-002 Rev. A 3/20/2024
CURVEPOINTS ONCE THE BURNER HAS STARTED.