Wayne LC2300M Manual page 30

Table of Contents

Advertisement

31. Adjust the High & Low Gas Pressure Switches according to actual firing conditions. For
close burner control, the High Gas Pressure Switch should be set at approximately 1 in.
W.C. above the set manifold pressure and the Low Gas Pressure Switch should be set
approximately 2 in. W.C. below the manifold pressure. Nuisance lockouts will occur if the
switch settings are too close to the manifold setting and if fluctuations in gas pressures
occur. Re-attach switch covers.
32. Record the installation data, the combustion readings, etc., and affix to this manual, or the
burner and/or appliance. Space has been provided at the beginning of this manual on Page
2 for start-up notes, dealer's name, address, telephone number, as well as the date of
installation.
SUGGESTION: ALL NEW INSTALLATIONS SHOULD BE RE-INSPECTED FOR PROPER
COMBUSTION AND BURNER OPERATION AFTER ONE OR TWO WEEKS OF NORMAL
For subsequent normal starting and shut off procedure, refer to the "Consumer Instructions" in the
back of this manual or the instruction plate attached to the burner.
TO RESTART THE BURNER AFTER A FLAME FAILURE, Push the reset switch on either the
control panel or the handheld AZL display. The burner should relight after power is restored and the
unit has a call for heat. If problems persist, refer to SECTION III – OPERATION AND
TROUBLESHOOTING.
To stop the burner in the event of an emergency, remove power from the main electrical disconnect,
turn "off" any added external "on/off" switch, and close any manual gas ball valve.
63899-002 Rev. A 3/20/2024
Gas Type
Natural Gas
LP Gas
OPERATION.
Excess Air Flue Gasses (%O2)
4 ± 1
30