easily be added into the system. The LMV3 compatible part number for purchase is 1000185-KIT. For
wiring a UV scanner into the control, please reference the LMV3 Technical Instructions link and QR
code found on Page 39. It is important to note that the sight glass must be removed when the UV kit is
installed. There will be no flame signal detected if the glass remains in place.
D: TROUBLESHOOTING
The most common fault codes have been noted below. For all LMV3 fault codes and diagnostic codes please
refer to the LMV3 Technical Instructions below on page 39. A QR code and a URL link have been provided for
a full electronic copy on Page 39.
Error
Diagnostic
Code
Code
(Loc:c:)
(Loc:d:)
2
Any #
0
1
3
4
7
Any #
20
Any #
D.1 DISPLAY OF FAULTS
The example shown below displays error code 4, diagnostic 3. Refer to the LMV Manual for a
comprehensive list of fault codes.
63899-002 Rev. A 3/20/2024
TABLE 4: COMMON FAULT CODES
Meaning
A flame failure occurred during lighting.
1. Check the wiring of the ignition transformer, pilot valve, and main valve(s).
No flame at end
2. Check manual shutoff valves for supply gas.
of safety time
3. Check the position of the air damper and close it further if necessary.
4. Check the flame detector signal in the presence of a known flame source.
Replace the flame detector if it does not produce the anticipated signal.
The air pressure switch input was de-energized when it should have been energized.
Air Pressure Off
Make sure the blower starts in phase 22 and the switch setpoint is set appropriately.
The air pressure switch input was energized when it should have been deenergized.
Air Pressure On
Make sure the blower turns off in phase 78 and the switch setpoint is set appropriately.
If necessary, increase the setting of parameter 213.
Air Pressure On
Prevention of
The air pressure switch input is energized, preventing the LMV3 from starting up.
Startup
1. Increase the setting of parameter 186:01 (fuel 0) or 187:01 (fuel 1). This increases
the FFRT. A maximum setting of 30 equals a 4 second FFRT.
Loss of flame
2. Check the flame detector signal in the presence of a known flame source. Replace
the flame detector if it does not produce the anticipated signal.
1. A fault occurred related to the low gas pressure switch. See diagnostic codes for
more information.
2. The low gas pressure switch (input X5-01.2) opened, causing a fault. Check gas
Gas Pressure
supply and open any manual shutoff valves. Check the setpoint and wiring of the low
Switch (Min)
gas pressure switch.
3. The low gas pressure switch was not made by the end of phase 22, preventing the
startup of the LMV3. See diagnostic code 0 for more corrective actions.
Corrective Action
Loc:c: This display shows the current
fault status.
38