10. Upon successfully entering the OEM Password the screen will briefly display "PArA" and
settle on "400: Set". Press and hold "Enter" until "P54" briefly shows on the display.
11. Once "P54" has appeared on the screen, "P-: -- --" will then appear. Briefly press "Esc"
("+" and "-" simultaneously).
12. Upon pressing "Esc", P0 should begin flashing on the screen. P0 is the pre-set ignition
point.
NOTE: IGNITION POINT (P0) IS NOT LOW FIRE (P1). P0 IS THE SETPOINT THE
BURNER USES TO INITIALLY LIGHT. P1 IS OFTEN LOWER THAN P0.
NOTE: IF ADJUSTMENTS TO EITHER THE FUEL OR AIR SETTINGS ARE REQUIRED IN THE
APPLICATION, THOSE ADJUSTMENTS MAY BE MADE BY HOLDING THE "F" FOR FUEL OR
"A" FOR AIR BUTTONS WHILE SIMULTANEOUSLY USING THE "+" AND "-" ARROWS TO
13. Toggle the "+" key to proceed to P1. P1 is the pre-set low fire point.
14. Toggle the "+" key to proceed to P9. P9 is the pre-set high fire point.
63899-002 Rev. A 3/20/2024
Before proceeding, HIGH FIRE AND LOW FIRE RATES HAVE BEEN
PRE-SET BY THE MANUFACTURER. High fire is set for 2.3MMBtu. If
the appliance rating is not capable of withstanding the pre-set high fire rate,
please continue to step 10 for reprogramming. Otherwise, proceed to step 16.
ADJUST ACCORDINGLY.