After confirming all safety systems are in place and you are ready to ignite the burner, press the "+"
button. The burner will go through the ignition cycle. Here, we will go thought Phase 38, 40, 42 and
44.
After Phase 44, the burner has ignited, and will remain lit at setpoint P0. Ignition parameters have
already been pre-set within the control. If the burner fails to light or to remain lit, note the fault
code(s) provided and refer to SECTION III – OPERATION AND TROUBLESHOOTING of this
manual for troubleshooting advice. If the fault code cannot be found in the Common Fault Codes
Table within SECTION III of this manual, please refer to the LMV3 Technical Instructions. A direct
web link and QR code have been attached below on page 39. A comprehensive list of fault codes can
be found beginning on the LMV3 Technical Instructions beginning on page 138.
NOTE: ON NEW GAS LINE INSTALLATIONS, AIR MAY BE TRAPPED IN THE GAS LINE; THE
BURNER MAY EXPERIENCE SEVERAL LOCKOUTS UNTIL ALL THE AIR IS PURGED FROM
63899-002 Rev. A 3/20/2024
Ph 38: Pre-Ignition
Ph 40: Initial safety. (Ignition
transformer is energized.) At this point
the spark electrode continues for 10
seconds. There will be a countdown to
the right of the "Ph 40" display.
Ph 42: Initial Safety. (Ignition
transformer no longer energized)
Ph 44: Phase 1
THE LINES.