Wire the mating female connector. Observe the instructions that are given by the manufacturer of the
mating female connector.
Insert each conductor into the appropriate pin. Refer to the following figure.
5-pin M12 male connector (A
coding)
5
4
1
M12 thread is internally con-
nected to FE
Tab. 5: Pin assignment, 5-pin M12 male connector (A coding)
Take a strand of the cable shielding and insert the strand into pin 1.
Screw the mating female connector to the 5-pin male connector, to the torque given by the manufacturer
of the mating female connector.
Do the functional earthing of the device. Refer to
6.3

Wire the variant Industrial Ethernet

NOTICE!
Requirements for the correct operation of the device.
Use a power supply unit with sufficient power.
Use only Industrial Ethernet shielded cables with a category CAT-5e or higher.
Connect each cable end to the functional earth.
For an MDC pay attention to the maximum permissible residual ripple on the operating voltage (residual
ripple < 2 %).
NOTICE!
UL approved versions must be supplied in one of the following ways:
"Limited Energy Circuit" (LEC), according to UL / IEC61010-1
"Limited Power Source" (LPS), according to UL / IEC60950
SELV / PELV with UL-approved overcurrent protection, designed according to UL / IEC61010-1, Table
18 (e.g. Block PM-0124-020-0)
NEC Class 2 power supply unit
32
Pin
Assignment
1
Shield
3
2
24 V
2
3
GND
4
CAN_H
6
5
CAN_L
6
Coding lug
Type 8756 Batch
Electrical connection
Connect the functional earth [} 35]