Commissioning; Commissioning Procedure - Burkert 8756 Batch Operating Instructions Manual

Mass dosing controller
Hide thumbs Also See for 8756 Batch:
Table of Contents

Advertisement

Type 8756 Batch

Commissioning

7
COMMISSIONING
Risk of injury or material damage when working on the device or system.
Read and observe the chapter
7.1

Commissioning procedure

The operation of the device is tested at the factory with medium. Residual medium can remain in the
device.
If the memory card is defective or lost, then buy a new one from your Bürkert sales office.
MDC with on/off valve
No zero adjustment is needed.
Pressurise the pipes with medium.
Make sure that the on/off valve is completely open.
Flush the pipes with medium.
Vent the pipes completely.
Check if the memory card is inserted.
Energise the device.
Variant büS /CANopen: Choose between CANopen communication and büS communication. Refer to
Set the CANopen communication or the büS communication [} 46]
MDC for modular actuator
No zero adjustment is needed.
Pressurise the pipes with medium.
Configure the connected actuator. Refer to Configure the actuator (MFC for modular actuator)
Flush the pipes with medium.
Vent the pipes completely.
Check if the memory card is inserted.
Energise the device.
Variant büS /CANopen: Choose between CANopen communication and büS communication. Refer to
Set the CANopen communication or the büS communication [} 46]
Safety [} 8]
before working on the device or system.
37