With Canopen Cables - Burkert 8756 Batch Operating Instructions Manual

Mass dosing controller
Hide thumbs Also See for 8756 Batch:
Table of Contents

Advertisement

Type 8756 Batch
Electrical connection
Colour of the büS cable conductor
black
white
blue
Tab. 3: Signals of the büS cable conductors
NOTICE!
If an own mating female connector is used, then observe the following requirements for the correct op-
eration of the device.
Use a mating female connector with shield connection.
Make sure that the büS cable passes through the mating female connector. The büS cable that is avail-
able from Bürkert has an external diameter of 8.2 mm.
Wire the mating female connector. Observe the instructions that are given by the manufacturer of the
mating female connector.
Insert each conductor into the appropriate pin. Refer to the following figure.
5-pin M12 male connector (A
coding)
5
3
4
2
1
6
M12 thread is internally con-
nected to FE
Tab. 4: Pin assignment, 5-pin M12 male connector (A coding)
Take a strand of the cable shielding and insert the strand into pin 1.
Screw the mating female connector to the 5-pin male connector, to the torque given by the manufacturer
of the mating female connector.
Do the functional earthing of the device. Refer to
6.2.3

With CANopen cables

Requirements for the correct operation of the device.
Use shielded CANopen cables. The cable shielding can be either a braid shielding or a foil shield-
ing.
To wire the device, mating female connectors are available from Bürkert.
NOTICE!
Requirements for the correct operation of the device.
Use a mating female connector with shield connection.
Observe the specifications for the cable and conductors, that are given by the manufacturer of the mat-
ing female connector.
Pin
Assignment
1
Shield
2
24 V
3
GND
4
CAN_H
5
CAN_L
6
Coding lug
Connect the functional earth [} 35]
Signal
GND
CAN_H
CAN_L
31