Connect The Functional Earth; Connect The External Actuator - Burkert 8756 Batch Operating Instructions Manual

Mass dosing controller
Hide thumbs Also See for 8756 Batch:
Table of Contents

Advertisement

Type 8756 Batch
Electrical connection
6.5

Connect the functional earth

WARNING!
Risk of ignition and risk of fire that are due to electrostatic discharge.
An electrostatic discharge of the device can ignite combustible gas vapours.
To avoid a build up of electrostatic charge, connect the housing to the functional earth.
If the functional earth is not attached, then the requirements of the EMC directive are not met.
Use a green-and-yellow cable that is as short as possible. And the cable cross-section must be at least
equal to the cross section of the power-supply cable.
With a flat screwdriver of size 6.5 mm, loosen the M4 screw.
Fig. 10: Location of the M4 screw for the connection of the functional earth
Attach the green-and-yellow cable to the M4 screw with a cable lug.
Tighten the M4 screw to a torque of 1,8 N·m...2 N·m (1,33 lbf·ft...1,47 lbf·ft).
6.6

Connect the external actuator

MDC for modular actuator
To wire the device, mating male connectors are available from Bürkert.
Wire the mating male connector according to the pin assignment of the M12 female connector. Observe
the instructions that are given by the manufacturer of the mating male connector.
8-pin M12 female connector
Tab. 8: Pin assignment, 8-pin M12 female connector
Screw the mating male connector to the 8-pin female connector, to the torque given by the manufacturer
of the mating male connector.
1
22 kΩ-pull-up resistor and free wheeling diode, both to 24 V, active low.
Pin
Assignment
1
24 V
2
GND
3
0-10 V output
4
0-10 V GND
5
Digital output (5 V level)
1
6
PWM (open collector)
7
Internal use only
8
Not connected
9
Coding lug
Housing
FE
M4 screw
35