Change The Network Parameters; Over The Product Web-Server - Burkert 8756 Batch Operating Instructions Manual

Mass dosing controller
Hide thumbs Also See for 8756 Batch:
Table of Contents

Advertisement

Type 8756 Batch
Electrical connection
5-pin M12 male connector
M12 thread is internally con-
nected to FE
Tab. 6: Pin assignment, 5-pin M12 male connector (A coding)
4-pin M8 female connector (D
coding)
3
4
5
5
2
1
5
M8 thread is internally connec-
ted to FE
Tab. 7: Pin assignment, 4-pin M8
If a protocol other than EtherCAT is used, plug an Ethernet cable in one or both sockets.
If the EtherCAT protocol is used, plug the incoming Ethernet cable (coming from the PLC) into the socket
marked ETH1 and plug the outgoing Ethernet cable into the socket marked ETH2.
6.4

Change the network parameters

Industrial Ethernet variant
The Industrial Ethernet variants Ethernet/IP and ModbusTCP have the same default IP address
192.168.1.100, Profinet devices have 0.0.0.0 by default.
Before commissioning the device, change its network parameters.
If several devices must be connected to the same Industrial Ethernet network, then connect one
device at a time and change its network parameters.
6.4.1

Over the product web-server

NOTICE!
Security risk due to default passwords.
Unauthorised persons can log in to the web server and change the parameters.
Change the default passwords.
If the web server is not needed, then disable access with the Bürkert Communicator software, refer to
Configuration with Bürkert Communicator [} 38]
Prerequisites:
Pin
Assignment
1
Shielding
2
24 V
3
GND
4
Not connected
5
Not connected
6
Coding lug
Pin
Assignment
1
Tx +
2
Rx +
3
Tx −
4
Rx −
5
Coding lug
33