Activate Address In Alarm Mode (H8/S6) - Panasonic MEW01777 Operating Instructions Manual

Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01777
30.7
Action
"
"
Menu
Scroll to menu H8.
"
"
Scroll to menu S6.
"
"
Write the zone number and
address (e.g. 123-45).
"
"
"
"
"
ESC
"
"
"
Reset
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V2.2.x

Activate address in alarm mode (H8/S6)

One alarm point (zone-address), not a whole zone, can be set in alarm.
It will be presented in this control unit as a fire alarm, the built-in
LED in the alarm point (e.g. a detector) will be turned on and all
outputs, standard and programmable, which would have been
activated by a normal fire alarm from the same alarm point will be
activated.
In all other control units in the system the alarm will be presented as a
Test mode alarm.
NOTE! A detector programmed for "Quiet alarm" will activate a
Quiet alarm instead of a fire alarm
Text in display
H8 Maintenance
S1 Dis- / Re-connect loop / zone line input
S2 Acknowledge SERVICE signal
S3 Clear weekly average
S4 Test of alarm devices
S5 Safe shut down of control unit
S6 Activate address in alarm mode
S7 Synchronize the control units
S8 Activate / Reset outputs
S6 Activate address in alarm mode
Select zone: 000 address: 00
(press ↵)
Select zone: 123 address: 45
(press ↵)
First alarm: 123-45
Latest alarm: 123-45
------------------------------------------------------------------------------------------
Select zone: 123 address: 45
(press ↵)
S6 Activate address in alarm mode
In all other control units the alarm will be presented as a Test mode
alarm:
1 zone in alarm
146
Comments
According to chapter
"Access", see page 88.
Press "
ESC
" to leave this
menu.
The fire alarm has to be
reset as a normal fire alarm
(press "
").
Reset
Scroll to another menu or
press "
".
ESC