Panasonic MEW01777 Operating Instructions Manual page 66

Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01777
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V2.2.x
control unit xx
The fault is to be found in the extinguishing system, which has a fault
output connected to a programmable supervised input in the EBL512
G3 system, in control unit no. xx. Also check the input connections.
NOTE! Close to the soft key area in the display there will be an
additional information text: Extinguishing fault
FAULT: Factory settings,
control unit xx
The factory settings have been "changed", in control unit no. xx, e.g.
because of some external disturbance. The main board has to be
replaced.
FAULT: Fan, technical number xxxxxx
The LED "Fault" is lit on a fan control module connected to control
unit xx. Fan no. xx has been activated but the corresponding I/O unit
3361 input has not been activated within the programmed time.
Check the fan and the cables / connections.
NOTE! In the Australian and New Zealand conventions this fault is
"not latched" irrespective of if all other faults are "latched".
FAULT: Fault warning routing equipment,
control unit xx
The fault is to be found in the Fault warning routing equipment. A
routing equipment fault output is connected to a programmable
supervised input in the EBL512 G3 system, in control unit no. xx.
Check the input connections as well. (Normally used for German
routing equipment connected to an expansion board 4583 input 0.)
FAULT: FB silence switch,
control unit xx
Only valid in the New Zealand convention.
New Zealand FB Silence switch ("outside switch") is turned on, in
control unit no. xx, i.e. from not activated to activated state.
FAULT: Fire brigade panel xx,
control unit xx
FBP=1826 / 1828 (Ext. Fire Brigade Panel)
The ext. FBP xx, connected to control unit no. xx, is programmed as
64
.