Panasonic Eco Solutions Nordic AB
MEW01777
Rev: -
5
LED indicator
L1
Fire (5 red)
L2
Extinguishing (red)
L3
Ventilation (yellow)
L4
Fire brigade tx (red)
L5
Operation (green)
L6
Alarms queued (2 red)
Operating Instructions Fire alarm system EBL512 G3, V2.2.x

LED indicators and push buttons

LEDs and push buttons can vary according to type and configuration
(convention / country / language).
See also Figure 2, page 17.
LED indicators on the Fire Brigade Panel (FBP)
Indicating
Fire alarms (see below)
Quiet alarm
See also chapter "Alarm types", page 41.
Output(s) for extinguishing equipment activated. (Or a
programmable input type "Extinguishing" is activated.)
Output(s) for fire/smoke ventilation equipment activated. (Or
a programmable input type "Ventilation" is activated.)
Output "Fire alarm" for fire brigade tx (routing equipment)
and/or corresponding programmable output(s) of type
"Routing equipment") is/are activated. (Or a programmable
input type "Activated routing equipment" is activated.)
Test of routing equipment in progress (see menu H1).
The c.i.e. is powered via the rectifier and/or the battery.
More than one alarm point / zone have activated fire alarm.
Use push button "Alarms queued" (P8) to scroll amongst the
alarm points (zone-address) or the soft key "Next zone" (P5)
to scroll amongst the zones.
NOTE! Fire alarms are:
Fire alarm (incl. test mode alarm)
Heavy smoke/heat alarm
Alert Annunciation (AA) alarm
Key cabinet alarm
18