Operating Instructions Fire alarm system EBL512 G3, V2.2.x

Alarm devices (H2/B4)

All outputs of type "Alarm device" can be collectively disabled.
Disabled output will stay in (or return to) the normal condition for the
output respectively.
Disabled outputs are listed in menu H4/U1 from which it is also
possible to get a print-out.
Text in display
H2 Disable or re-enable
B1 Zone or Zone/Address
B2 Output
B3 Output type
B4 Alarm devices
B5 Routing equipment
B6 Alert annunciation function
Escape
menu
B4 Alarm devices
Disable
All alarm devices
Disable
All alarm devices
-- Re-enable list --------------------------------------------------
All alarm devices
102
Comments
According to chapter
"Access", see page 88.
Via menu B4 can all
outputs of type "Alarm
device" be collectively
disabled in all control
unit.
Press "
" to disable,
which will be indicated
with "√" and a beep.
The "type" will directly
be shown in the Re-
enable list
Use the soft key "|" to
toggle between Disable
and Re-enable list.