19.4
19.5
Operating Instructions Fire alarm system EBL512 G3, V2.2.x
In a redundant network two Projects have to be created and installed.
The Projects have to be identical but with different Project names.
One project has to be installed for Network no. 0 and one has to be
installed for Network no. 1.
If a redundant TLON Network shall be used, a PC is connected to the
modular connector "J11" (Network no. 1) and the same procedure as
for Network no. 0 is done for Network no. 1.
NOTE! After the TLON Network installation (download) it is highly
recommended to restart the control units.

Add a Control Unit in a TLON network

When adding a new control unit to a "running" installation you have
to have the same software (S/W) version in all control units. Often the
new control unit has a newer version than the existing control units.
Normally the latest version is the best to use, i.e. the control units in
the "running" installation have to be upgraded. As an alternative, it is
possible to download an earlier S/W version in the new control unit.
Both alternatives are described in Planning Instructions MEW01776.
Open the current project in TLON Manager, add one control unit and
install (download) it according to the separate TLON network
Operating Instructions MEW01361. Also see 19.2.1 above.
Open the SSD for the current system via EBLWin. Add one control
unit (and the units connected to it) and download the new SSD
according to Planning Instructions MEW01776.

Make two TLON networks one.

It is very important that two or more presentation numbers (Zone or
Zone-Address) in the systems are not the same. The system properties
have to be the same.
Use one of the systems, e.g. the largest and add to it the control units
etc. from the other system.
If it is known from the beginning that two systems shall be one in the
future, it is possible to give the control units in the system
respectively, the "final" control unit numbers right from the beginning
in order to get the correct technical numbers in the system documents.
NOTE! Two or more presentation numbers (Zone or Zone-Address)
in the systems must not be the same.

Delete a Control Unit in a TLON network

Physically disconnect the control unit. This action will generate faults
in the other control units. Acknowledge the faults.
36
It is not possible to merge two TLON Networks into one or copy one
system and paste into another system.