Co-Incidence Alarm (2-Address / -Zone Dependence); Delayed Alarm - Panasonic MEW01777 Operating Instructions Manual

Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01777
Rev: -
16.5.2.1
16.6
16.7
Operating Instructions Fire alarm system EBL512 G3, V2.2.x
Restoring the key after a fire alarm
When all fire alarms in the system are reset (see chapter "Alarm
reset", page 53), the key has to be restored into the key cabinet within
5 minutes. If not, a fault will be generated, see chapter "Key cabinet
alarm reset", page 55.
Co-incidence alarm (2-address / -zone
dependence)
The co-incidence alarm function is programmed via EBLWin for the
alarm points / zones in question.
When only one zone or one zone / address (alarm point) is in alarm
status, the c.i.e. buzzer sounds (0.8 / 5 sec.) and there is a Co-
incidence alarm presentation in the display. Note that LEDs "Fire"
(L1) are not indicating a co-incidence alarm.
The co-incidence alarm will be automatically Reset after 5 minutes
(i.e. if the zone / alarm point is no longer in alarm status) or via the
"Reset" button (P3). See chapter "Alarm reset", page 53.
An example; Co-incidence alarm zone 123, address 45:
Co-incidence alarm
Zone
123-45
User definable alarm text for 123-45.
Menu
If more than one Co-incidence alarm not dependent on each other are
activated, the LEDs "Alarms queued" (L6) are blinking and the Co-
incidence alarms will be automatically scrolled (each 5
If two or more zones or alarm points (zone / addresses) dependent on
each other are in alarm status at the same time, normal fire alarm (see
above) will be activated in the system.
function can be turned on / off via a time channel.

Delayed alarm

Delayed alarm is an option that has to be enabled (via EBLWin) for
the alarm point respectively.
49
Address
SMOKE
th
second).
The co-incidence alarm