Perform ZONE TEST (Test mode)
(H7)
Normally, zones are tested during the monthly test via menu H1. Via
this menu (H7) it is also possible to perform the zone test. Up to 100
zones can be set in test mode.
In test mode, only the alarm points are tested, i.e. no outputs (e.g.
sounders) will be activated during the test. (Alarm devices can be
tested via menu H8/S4 and any output via menu H8/S8 or via
EBLWin when you are logged on.)
If a real fire alarm is activated by an alarm point not in test mode,
the normal fire alarm functions will be activated, i.e. fire alarm
presentation, outputs (sounders) activated, routing equipment (fire
brigade tx) activated, etc.
See also chapter "The information area priority order", page 24.
NOTE! If the control unit door is left open, the output(s) for routing
equipment (fire brigade tx) might be disabled (if set so in EBLWin).
One or more zones in test mode are indicated by the LED "Test mode"
(L8). The green polling LED in the 440x detectors will be turned off
in test mode.
The zones are set one by one in test mode and the test mode has to be
ended for each zone one by one.