Inverter Safety - Goodwe ETC Series User Manual

Hybrid/ac-coupled inverter 50kw&100kw
Hide thumbs Also See for ETC Series:
Table of Contents

Advertisement

02 Safety Precaution

2.3 Inverter Safety

• The voltage and frequency at the connecting point should meet the grid connection
requirements.
• Additional protective devices like circuit breakers or fuses are recommended on the AC
side. Specification of the protective device should be at least 1.25 times the maximum AC
output current.
• Make sure that all the grounding cables are tightly connected. When there are multiple
inverters, make sure that all the grounding points on the enclosures are equipotental
connected.
• You are recommended to use copper cables as AC output cables. Contact the manufacturer
if you want to use other cables.
• Do not start the BACK-UP function if the PV system is not configured with batteries.
Otherwise, the manufacturer shall not be liable for the related system risks.
• All labels and warning marks must be clear and distinct after the installation. Do not block,
alter, or damage any label.
• Warning labels on the inverter are as follows:
HIGH VOLTAGE HAZARD.
Disconnect all incoming
power and turn off the
product before working on it.
Read through the user
manual before any
operations.
High-temperature hazard. Do
not touch the equipment to
avoid being hurt.
CE Mark
WARNING
DANGER
4
User Manual V1.0-2023-04-30
Delayed discharge. Wait
5 minutes after power off
until the components are
completely discharged.
Potential risks exist. Wear
proper Personnel Protective
Equipment before any
operations.
Grounding point.
Do not dispose of the inverter
as household waste. Discard
the product in compliance
with local laws and
regulations, or send it back to
the manufacturer.