02 Safety Precaution

2.3 Inverter Safety

• The voltage and frequency at the connecting point should meet the on-grid requirements.
• Additional protective devices like circuit breakers or fuses are recommended on the AC
side. Specification of the protective device should be at least 1.25 times the maximum AC
output current.
• Make sure that all the groundings are tightly connected. When there are multiple inverters,
make sure that all the grounding points on the enclosures are equipotential bonding.
• The alarm can be cleared automatically if the inverter triggers a fault for less than 5 times
within 24 hours. The inverter will shutdown for protection after the 5th electric arc fault.
The inverter can operate normally after the fault is solved.
• BACK-UP is not recommended if the PV system is not configured with batteries. Otherwise,
the risk in system power usage is beyond the equipment manufacturer's warranty scope.
• All labels and warning marks should be visible after the installation. Do not cover, scrawl,
or damage any label on the equipment.
• Warning labels on the inverter are as follows:
DANGER High voltage hazard.
Disconnect all incoming
power and turn off the
product before working on it.
Read through the user
manual before any
operations.
High-temperature hazard. Do
not touch the product under
operation to avoid being
burnt.
CE certification mark
WARNING
DANGER
4
User Manual V1.0-2022-08-30
Delayed discharge. Wait 5
minutes after power off until
the components are completely
discharged.
Potential risks exist. Wear
proper PPE before any
operations.
Grounding point.
Do not dispose of the inverter
as household waste. Discard
the product in compliance with
local laws and regulations,
or send it back to the
manufacturer.