DeviceNet ArmorBlock Network and Auxiliary Powered I/O Module 11

Communicate with Your Module

This module's I/O is exchanged with the master through a cyclic, polled, or
change-of-state connection.
Cyclic - allows configuration of the block as an I/O client. The block will
produce and consume its I/O cyclically at the rate configured.
Polled - a master initiates communication by sending its polled I/O message
to the module. The module consumes the message, updates outputs, and
produces a response. The response has input data.
Change-of-State - productions occur when an input changes or a fault
condition occurs. If no input or fault condition change occurs within the
expected packet rate, a heartbeat production occurs. This heartbeat
production tells the scanner module that the I/O module is alive and ready to
communicate. Consumption occurs when data changes and the master
produces new output data to the I/O block.
Refer to the Module Data Definitions table for more information.
1732D-8X81212D Data Definitions
Byte
Bit 7
Produce 0
I7
Produce 1
In short
Consume 0
O7
Where:
I=Input Data; 0=Off, 1=On
In Short 0=Working, 1=Sensor Source Voltage Fault
Out Short 0=Working, 1=Output Fault (Short)
O=Output Data; 0=Off, 1=On
Bit 6
Bit 5
I6
I5
Out short
O6
O5
Bit 4
Bit 3
Bit 2
I4
I3
I2
O4
O3
O2
Publication
1732D-IN009A-EN-E - April 2009
Bit 1
Bit 0
I1
I0
O1
O0