Bfm #70 (Ch1) And Bfm #71 (Ch2): Input Type Selection - Mitsubishi Electric MELSEC FX2N-2LC User Manual

Temperature control block
Hide thumbs Also See for MELSEC FX2N-2LC:
Table of Contents

Advertisement

FX2N-2LC Temperature Control Block
7.2.33

BFM #70 (CH1) and BFM #71 (CH2): Input type selection

In BFM #70, select the input type of CH1. In BFM #71, select the input type of CH2.
The initial value is "2".
Table 7.7:
Set
Sensor
value
type
0
1
K
2
3
4
5
6
7
J
8
9
10
11
R
12
13
S
14
15
E
16
17
18
19
20
T
21
22
23
*2 For B inputs, 0 to 399
*3 For PLII inputs, 0 to 32
*4 For WRe5 to WRe26 inputs, 0 to 32
Input range
Unit
-1
-200.0 to 200.0
10
-100.0 to 400.0
-1
10
°C
-100 to 1300
°F
-100 to 800
°F
-100 to 2400
-1
-200.0 to 200.0
10
-100.0 to 400.0
-1
10
-1
-100.0 to 800.0
10
°C
-100 to 1200
°F
-100 to 1600
°F
-100 to 2100
°C
0 to 1700
°F
0 to 3200
°C
0 to 1700
°F
0 to 3200
-1
-200.0 to 200.0
10
°C
0 to 1000
°F
0 to 1800
-1
-200.0 to 200.0
10
-1
-200.0 to 400.0
10
-1
0.0 to 400.0
10
-300.0 to 400.0
-1
10
-1
-300.0 to 700.0
10
0.0 to 700.0
-1
10
°
C (0 to 799
°
F is outside the precision compensation range.
Set
Sensor
value
type
°C
24
B
°C
25
26
N
27
28
PL II
°C
29
°C
30
WRe5-26
°C
31
32
U
33
34
L
35
36
37
JPt100
38
°C
39
40
41
Pt100
°C
42
°C
43
°C
°F
°F
°F
°
F) is outside the precision compensation range.
°
F is outside the precision compensation range.
Buffer Memory (BFM) 7
Input range
Unit
°C
0 to 1800
°F
0 to 3000
°C
0 to 1300
°F
0 to 2300
°C
0 to 1200
°F
0 to 2300
°C
0 to 2300
°F
0 to 3000
-1
-200.0 to 600.0
10
-1
-300.0 to 700.0
10
-1
0.0 to 900.0
10
°F
0 to 1600
-1
-50.0 to 150.0
10
-1
-200.0 to 500.0
10
-1
-300.0 to 300.0
10
°F
-300 to 900
-1
-50.0 to 150.0
10
-1
-200.0 to 600.0
10
-1
-300.0 to 300.0
10
°F
-300 to 1100
7-22
°C
°F
°C
°C
°C
°F
°C
°C
°F

Advertisement

Table of Contents
loading