Operation Panel Indication
Name
Description
Check point
Corrective action
Operation Panel Indication
Name
Description
Check point
Corrective action
PS
PU stop
Pr. 75 "reset selection/PU stop selection" had been set and a stop
was made by pressing the
parameter unit (FR-PU04) during operation in the external
operation mode.
Check for a stop made by pressing the
panel during external operation.
Refer to page 103.
UV
Undervoltage
If the power supply voltage of the inverter reduces, the control
circuit will not operate properly and will result in decreased motor
torque or increased heat generation. To prevent this, if the power
supply voltage reduces below about 230VAC (about 115VAC for
the single-phase 200V power input series), this function stops the
inverter output.
• Check for a start of large-capacity motor.
• Check that the power supply capacity is as indicated in the
specifications (Refer to page 168.).
Check the power supply system equipment such as the power
supply.