Load Pattern Selection (Pr. 14 ) - Mitsubishi Electric FR-S500E Instruction Manual

Frequency inverter
Table of Contents

Advertisement

2.3.9
Load pattern selection (Pr. 14
You can select the optimum output characteristic (V/F characteristic) for the
application and load characteristics.
Pr.14=0
For constant-torque
loads
(e.g. conveyor, cart)
100%
Base frequency
Output frequency (Hz)
(Factory setting)
Parameter
Name
Load pattern
14
selection
CAUTION
1. When automatic torque boost control is selected, this parameter setting is
ignored.
2. Pr. 46 "second torque boost" is made valid when the RT signal turns on.
The RT signal acts as the second function selection signal and makes the
other second functions valid.
Related parameters
Automatic torque boost ⇒ Pr. 98 "automatic torque boost selection (motor capacity)"
Boost setting ⇒ Pr. 0 "torque boost", Pr. 46 "second torque boost" (refer to page 61)
Assignment of RT signal to terminal when second torque boost is used
⇒ Pr. 60 to Pr. 63 (input terminal function selection) (refer to page 96)
Pr.14=1
For variable-torque
loads
(Fan, pump)
100%
Base frequency
Output frequency (Hz)
Factory
Setting
Setting
Range
1
0, 1, 2, 3
(refer to page 119)
Explanation of functions (parameters)
)
Pr.14=2
For lift
100%
Forward
rotation
Reverse
Pr.0
rotation
Pr.46
Base frequency
Output frequency (Hz)
Boost for forward rotation
...Pr. 0 (Pr.46) setting
Boost for reverse rotation
...0%
0: For constant-torque loads
1: For variable-torque loads
2: For vertical lift loads
3: For vertical lift loads
71
Pr.14=3
For lift
100%
Reverse
rotation
Forward
Pr.0
rotation
Pr.46
Base frequency
Output frequency (Hz)
Boost for forward rotation
...0%
Boost for reverse rotation
...Pr. 0 (Pr.46) setting
Remarks
Setting is
enabled when
Pr. 30 = "1".
2

Advertisement

Table of Contents
loading

Table of Contents