Step 6. Prepare the Backup Gateway for Mounting

1. Remove the Backup Gateway from its packaging and verify that the contents are complete
and undamaged (see "Backup Gateway Box Contents," above).
2. Take a photo and record the serial number of the Backup Gateway in the back of the
Owner's Manual that came with the system. The serial number can be found on a label on the
inside of the enclosure door, and also on the outside of its packaging.
3. Open the Backup Gateway enclosure and remove the enclosure door.
4. Remove the screw at the bottom of the dead front panel and remove it from the enclosure.
Figure 24: Removing the Dead Front Panel from the Enclosure
5. Take photos and record the serial number and short ID number of the Energy Meter in the
back of the Owner's Manual that came with the system. The Energy Meter serial number and
short ID number appear on the side of the meter Wi-Fi sensor housing.
6. Determine whether cable entry to the Backup Gateway will be from the top, bottom, or side
of the enclosure. If cable entry will be from the top, skip to Step 7, "Mount the Backup
Gateway."
7. (Optional) To configure the Backup Gateway for cable entry from the bottom or sides, do
the following:
Remove the four fasteners holding the back panel assembly in place and remove it
from the enclosure.
Rotate the back panel assembly 180 degrees and reinstall it in the enclosure.