Current Transformer Orientation
CTs must be installed with the label on the CT housing pointing toward the power source,
according to the following table and diagram (Fig. 41).
Figure 41: CT Orientation in Relation to Power Flow
CT Usage
Site CTs
Solar CTs
Load CTs
Current Transformer Capacity
Each CT included with the Gateway and the available accessory kits has a capacity of 200 A.
If the wiring configuration allows, it is possible to pass multiple conductors of the same type
through a single CT, provided the sum of the conductor's current ratings does not exceed the
CT current handling capacity. This is especially useful for systems with multiple solar inverters.
Figure 42: Multiple Conductors Passing Through a Single CT
CT Orientation
CT label facing toward the service entrance/grid
CT label facing toward the solar inverter
CT label facing away from the loads