Download Print this page

Chapter 5  Technical Data - Helios IVR EC Installation And Operating Instructions Manual

Centrifugal jet fans

Advertisement

Available languages

Available languages

Installation and Operating Instructions
CHAPTER 5
TECHNICAL DATA
IVR EC – Jet Fans
− Dispose of the fan components according to the valid rules and laws.
− A max. storage temperature of 60 °C is permitted during standstill. In case of a higher standstill temperature, the
bearings or the motor must be cooled down.
− Check unit prior to recommissioning and ensure that safety devices have been installed and they are functional.
Expiry of service life, disposal
Parts and components of the fan, whose service life has expired, e.g. due to wear and tear, corrosion, mechanical
load, fatigue and/or other effects that cannot be directly discerned, must be disposed of expertly and properly after
disassembly in accordance with the national and international laws and regulations. The same also applies to auxiliary
materials in use. Such as oils and greases or other substances. The intended and unintended further use of worn parts,
e.g. impellers, rolling bearings, filters, etc. can result in danger to persons, the environment as well as machines and
systems. The corresponding operator guidelines applicable on-site must be observed and used.
51 Technical data
Nominal diameter
Protection class
Insulation class
Ambient temperature
Weight
Electrical data
Nominal voltage
Frequency
Nominal current consumption at 20 °C
Rated output
Wiring diagram
Motor
Rated speed
Ventilation data
Flow rate
Outlet velocity
Thrust
Practical throw distance with min. u= 0.8 m/s 40 m
Sound power level Hz
Total
IVRW EC 400
84
IVRD EC 450
83
* at 3 m distance free field conditions
General technical data
Maximum pre-fuse
Max. limit load integral of the start-up
current approx.
Frequency
Input resistance for speed specification
signal
Specification signal
PWM
Power supply for external units
Digital input "D1"
Electromagnetic compatibility
for the standard voltages
230 / 400 V according to IEC 60038
Harmonic currents
IVRW EC 400
400 mm
IP54
F
-20 °C to +40 °C
28 kg
230 V
50 Hz
6.4 - 4.6 A
1.25 kW
SS-1300
1,950 U/min
4,700 m
3
/h
33 m/s
50 N
63
125
250
500
dB(A) at 1/2 and 1/1 V
49
63
78
78
48
65
80
76
16 A for all types 1 ~ and 3 ~
1.22 A2s
16 kHz
Ri > 100 kΩ
Voltage: 15...28 V DC
Frequency: 1...10 kHz
Duty cycle: 0...100 %
+10 V, Imax 10 mA (short-circuit proof)
+24 V ±20 %, Imax 70 mA
Input resistance: Ri ca. 4 kΩ
Voltage range high level: 10...30 V DC
Voltage range low level: 0...4 V DC
Emitted interference pursuant to EN 61000-6-3 (residential area)
Interference immunity pursuant to EN 61000-6-2 (industrial area)
For 1 ~ types
Active power factor adjustment for sinusoidal current consumption
(PFC = Power - Factor - Controller), harmonic currents pursuant to
EN 61000-3-2 are guaranteed.
For 3 ~ types
According to EN 61000-3-2 (installation instructions / electrical installa-
tion /EMC compliant installation / harmonic currents for 3 ~ types).
11
IVRD EC 450
450 mm
IP54
F
-20 °C to +40 °C
33 kg
400 V
50 Hz
2.9 - 2.3
1.80 kW
SS-1299
1,800 U/min
6,300 m
3
/h
36 m/s
75 N
49 m
1000
2000
4000
8000
max
76
77
75
67
74
75
72
69
EN
Sound pres-
sure level*
64
68

Advertisement

Chapters

loading