Bearing Vibrations; Standstill And Disposal - Helios IVR EC Installation And Operating Instructions Manual

Centrifugal jet fans

Advertisement

Available languages

Available languages

Installation and Operating Instructions
EN
m
WARNING
nm
m
DANGER
IVR EC – Jet Fans
Bearing temperature
too high
Status output with blink code
LED Code
Relay K1 *
OFF
Inactive, 11 - 14 interrupted
ON
Active, 11 - 14 bridged
1 x
Active, 11 - 14 bridged
2 x
Active, 11 - 14 bridged
3 x
Inactive, 11 - 14 interrupted
4 x
Inactive, 11 - 14 interrupted
5 x
Inactive, 11 - 14 interrupted
6 x
Inactive, 11 - 14 interrupted
7 x
Inactive, 11 - 14 interrupted
8 x
Inactive, 11 - 14 interrupted
9 x
Active, 11 - 14 bridged
11 x
Inactive, 11 - 14 interrupted
12 x
Inactive, 11 - 14 interrupted
13 x
Inactive, 11 - 14 interrupted
14 x
Inactive, 11 - 14 interrupted
17 x
Inactive, 11 - 14 interrupted
* K1: for factory-programmed function: Fault signal not inverted.

45 Bearing vibrations

Motor output
Mounted
<= 300 kW
Fixed
<= 300kW
Fixed
<= 300 kW
on vibration damper
<= 300kW
on vibration damper
46 Spare parts
Optimal operational safety of the fans is only guaranteed with Helios spare parts and repair work carried out by the
manufacturer. Spare parts can be ordered from the manufacturer using the order number or type plate data.

47 Standstill and disposal

m
Risk of personal injury!
When dismantling, limbs/fingers can be crushed, drawn in, trapped or severed due to the unintended activation of the
fan.
When dismantling, limbs can be injured between components. Wear protective footwear and gloves.
m
Danger to life due to electric shock!
When dismantling, live parts can be exposed, which can result in electric shock if touched. Before dismantling,
isolate the unit from the mains power supply and protect against being switching on again!
Electrical work must only be carried out by an authorised electrician.
− Fully isolate electrical connection from mains power supply. The unit must be disconnected from the mains power
supply before dismantling or standstill.
− Use appropriate lifting equipment and fastening devices to dismantle the fan.
− Observe the instructions in the electric motor maintenance manual for decommissioning the motor.
Bearing damage
Imbalance
Vibration
Installation site
Normal
All
Normal
All
10
• Check bearing, replace if
necessary
• Contact manufacturer
• Check bearing, replace if
necessary
Cause
No mains voltage
Normal operation without fault
No enable = OFF
Temperature management active
HALL-IC fault
Phase failure (only for 3 ~ types)
Motor blocked
IGBT fault
Intermediate circuit undervoltage
Intermediate circuit overvoltage
IGBT cooling period
Motor start fault
Mains voltage too low
Mains voltage too high
Peak current fault
Temperature alarm
Alarm
7.1 mm/s
4.5 mm/s
11.8 mm/s
7.1 mm/s
Specialist
Specialist
Specialist
Deactivation
9.0 mm/s
7.1 mm/s
12.5 mm/s
11.0 mm/s