Expansions / Accessories
10.1.6

Functional test

The functioning of the restart lock must be tested during setup, after every alteration in the
wiring of the system, or after exchanging one or more components of the system.
1.
2.
3.
4.
5.
6.
10.1.7

Connection diagram (principle)

Application examples for category 1 see chapter 10.1.8.
94
Stop all drives, with setpoint 0V, disable drives, mechanically block any suspended loads
Activate the -AS- option.
Open protective screens (but do not enter hazardous area)
Pull off the X10 connector from an amplifier: the mains contactor must drop out
Reconnect X10. Switch on mains contactor again.
Repeat steps 4 and 5 for each individual servo amplifier.