Appendix H
BACnet map
Analog objects
Instance
Object name
0
Sensitivity
1
Phase A High Surge Count
2
Phase A Medium Surge Count
3
Phase A Low Surge Count
4
Phase B High Surge Count
5
Phase B Medium Surge Count
6
Phase B Low Surge Count
7
Phase C High Surge Count
8
Phase C Medium Surge Count
9
Phase C Low Surge Count
10
Phase A % Protection
11
Phase B % Protection
12
Phase C % Protection
13
Phase N-G % Protection
14
Phase A Total Surge Counts
15
Phase B Total Surge Counts
16
Phase C Total Surge Counts
17
RTC Time
18
Set Time
19
Total Low Surge Counts
20
Total Medium Surge Counts
21
Total High Surge Counts
22
Total Surge Counts
23
System Faults
24
Method of IP Allocation
Binary objects
Instance
Object name
0
Clear Surge Log Events
1
Clear Surge Counts
2
Phase A Green Led Status
3
Phase A Yellow Led Status
4
Phase A Red Led Status
5
Phase B Green Led Status
6
Phase B Yellow Led Status
7
Phase B Red Led Status
8
Phase C Green Led Status
9
Phase C Yellow Led Status
10
Phase C Red Led Status
11
NG Green Led Status
12
NG Yellow Led Status
13
NG Red Led Status
14
Alarm status
15
Silences Alarm
16
Clear General Log
AV = Analog value
BV = Binary value
Object description
Object type
Surge sensitivity
AV
Phase A high surge count
AV
Phase A medium surge count
AV
Phase A low surge count
AV
Phase B high surge count
AV
Phase B medium surge count
AV
Phase B low surge count
AV
Phase C high surge count
AV
Phase C medium surge count
AV
Phase C low surge count
AV
Percentage of protection available
AV
on phase A
Percentage of protection available
AV
on phase B
Percentage of protection available
AV
on phase C
Percentage of protection available
AV
on NG
Phase A total surge counts
AV
Phase B total surge counts
AV
Phase C total surge counts
AV
RTC time
AV
Set time
AV
Total low surge counts
AV
Total medium surge counts
AV
Total high surge counts
AV
Total surge counts
AV
System faults
AV
Allows to set the method used to
AV
allocate an IP address
Object description
Object type
Clear surge log events
BV
Clear surge counts
BV
Phase A green led status
BV
Phase A yellow led status
BV
Phase A red led status
BV
Phase B green led status
BV
Phase B yellow led status
BV
Phase B red led status
BV
Phase C green led status
BV
Phase C yellow led status
BV
Phase C red led status
BV
NG green led status
BV
NG yellow led status
BV
NG red led status
BV
Alarm status
BV
Silences the alarm
BV
Clear general log
BV
Instruction Booklet IB158002EN
Unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
No unit
Inactive text Active text
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Protected
Protection loss
Silence?
Silenced
OFF
ON
Effective September 2023
Access
COV
type
increment
R/W
1
RO
1
RO
1
RO
1
RO
1
RO
1
RO
1
RO
1
RO
1
RO
1
RO
1
RO
1
RO
1
RO
1
RO
1
RO
1
RO
1
RO
1
R/W
1
RO
1
RO
1
RO
1
RO
1
RO
1
R/W
1
Access type
R/W
R/W
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
R/W
R/W