Specifications

Table 7. Specifications
Description
Surge current capacity per phase
Nominal discharge current (I
)
n
Short circuit current rating (SCCR)
SPD type
Enclosure types
Circuit breaker—30 A
Circuit breaker load and line
 Terminal torque specifications
 Standard split-phase voltages available
 Single-phase
 Three-phase wye system voltages available
 Three-phase delta system voltages
 Three-phase high-leg delta system voltages
Input power frequency
Power consumption (standard with surge counter units)
 208Y, 220Y, 230L, 240S, 240D, and 240H voltage codes
 400Y, 480Y, and 480D voltage codes
 600Y and 600D voltage codes
Power consumption (Power Xpert SPD units)
 208Y, 220Y, 230L, 240S, 240D, and 240H
 400Y, 480Y, and 480D
 600Y and 600D
Protection modes
Maximum continuous operating voltage (MCOV)
230 V single-phase
127/220 V wye, 120/240 V single split-phase
120/240 V high-leg
230/40 V wye, 277/480 V wye
347/600 V wye
240 V delta
480 V delta
600 V delta
Ports
Operating temperature and humidity
Storage temperature
Operating altitude
Weight
Form C relay contact ratings
Form C terminal block ratings
Form C relay contact logic
EMI/RFI filtering attenuation (Standard with Surge Counter)
Ethernet port
Standards/agency certifications
Warranty
RoHS compliant
22
EATON www.eaton.com
Specification
100, 120, 160, 200, 250, 300, 320, 400, 600, 800 kA ratings available
20 kA
200 kA
Basic feature package = Type 1 (can also be used in Type 2 applications)
Standard with Surge Counter and Power Xpert SPD feature package = Type 2
NEMA 4, NEMA 4X enclosure, Power Xpert SPD available in NEMA 1 enclosures only
Eaton catalog number: FDC3030L
#10 AWG 35 lb-in; #8 AWG 40 lb-in; #6–#4 AWG 45 lb-in; #3–I/0 AWG 50 lb-in (SPD maximum wire range #10–1/0 AWG)
120/240
230
120/208, 127/220, 230/400, 277/480, 347/600
240, 480, 600
120/240 high-leg phase wire will be identified with a tag from the factory
50/60 Hz, 60 Hz Power Xpert SPD
0.6 W
1.7 W
2.1 W
4 W
4 W
4 W
Split-phase L-N, L-G, N-G, L-L,
Single-phase L-N, L-G, N-G,
Three-phase delta L-G, L-L ,
Three-phase wye L-N, L-G, N-G, L-L,
Three-phase high-leg delta L-N, L-G, N-G, L-L,H-N, H-G, H-L
320 V L-N, 320 V L-G, 320 V N-G
150 V L-N, 150 V L-G, 150 V N-G, 300 V L-L
150 V L-N, 150 V L-G, 150 V N-G, 300 V L-L, 320V H-N, 320 V H-G, 470 V H-L
320 V L-N, 320 V L-G, 320 V N-G, 640 V L-L
420 V L-N, 420 V L-G, 420 V N-G, 840 V L-L
300 V L-G, 300 V L-L
640 V L-G, 640 V L-L
840 V L-G, 840 V L-L
1 or 2
–20 °C to 50 °C (–4 °F to 122 °F), 5% through 95%, noncondensing
–20 °C to 50 °C (–4 °F to 122 °F)
Up to 16,000 ft (5000 m), Power Xpert up to 6561 ft (2000 m)
Not to exceed 52 lb
150 Vac at 0.46 A, 30 Vdc at 1A
Rated 300 V, 16 A, 30–12 AWG solid or stranded wire, torque range 5–7 lb-in
Power on, normal state, NO contact = OPEN, NC contact = CLOSED Power off, fault state, NO contact = CLOSED, NC contact = OPEN
Up to 50 dB from 10 kHz to 100 MHz
Data rate 10/100 Mbps, wire type: equal or exceed level 5 unshielded twisted pair (UTP), Category 5, use of STP shielded twisted
pair (STP) will improve EMI performance, connector type: RJ45 modular, ground metal shield
UL 1449 5th Edition—standard for surge protective devices
UL 1283 7th Edition—standard for EMI filters (Type 2 SPDs only)
CSA Electrical Notice NO. 516 Edition 1—surge/transient voltage suppressor
CSA 22.2 No. 8-13 electromagnetic interference (EMI) filters—Edition 5 issue date 2013/11/01
15 years from the date of delivery to the purchaser, 20 years when you register by clicking "Register your surge protective device"
link on www.eaton.com/spd
Yes
Installation instructions for
SPC Max Series surge protective device