Instruction Booklet IB158002EN
Effective September 2023

Troubleshooting

Many SPD failures result from improper installation . Once the SPD
is installed properly, it is a highly reliable unit . The most common
reason for SPD failure is a temporary overvoltage (TOV) condition .
If the SPD does not function properly, first confirm that it is installed
properly . See Installation on page 3 .
If the SPD malfunctions after it has been operating routinely, refer
to Table 5 . This troubleshooting chart identifies possible causes
and solutions to the malfunction . Further assistance may be
obtained by calling Eaton's Technical Resource Center (TRC)
and speaking to a surge protection application engineer at
1-800-809-2772 or email SPD@eaton.com, including being
directed to the warranty process if applicable .
Table 5. Troubleshooting chart for Basic and Standard with Surge Counter feature packages
Condition
Front mounted display
Green LEDs ON (1 per phase) and one Green LED ON for
Neu/Gnd Protection
Audible Alarm OFF, Form C (NC) contact in the CLOSED state
Phase Green LED is OFF, same Phase Red LED is ON,
Audible Alarm is ON
Neu/Gnd Green LED is OFF, Neu/Gnd Red LED is ON,
Audible Alarm is ON (for models with Neutral connections)
All phase Green LEDs OFF, all phase RED LEDs ON,
Audible Alarm is ON
Red LEDs are ON, Audible Alarm is OFF
All Green and Red LEDs are OFF, LCD display is OFF
One phase has neither a green or red LED lit
All phase LEDs are green, audible alarm is on
Internal SPD status indicator
SPD Status: SPD1 and SPD2 LEDs off
SPD Status: SPD1 red LED on
SPD Status: SPD2 red LED on
Red LED on the front panel, but both SPD Status red LEDs are off 10 pin ribbon cable(s) disconnected or installed wrong
a If the device is equipped with two surge protective devices, open the enclosure and determine which SPD Status LED is illuminated.
20
EATON www.eaton.com
Probable cause
Normal operation
Normal operation
Phase protection compromised or lost
Extended Temporary Overvoltage (TOV)
Significant surge event
Neu/Gnd protection is compromised or lost
Significant surge event
All phase protection is compromised or lost
SPD rated voltage is less than system voltage
Extended Temporary Overvoltage (TOV)
Significant surge event
Audible Alarm Silence button has been depressed and
Alarm is silenced
SPD is not connected to a power source
Ribbon cable is not connected properly.
Ribbon cable is mis-aligned with connector
Insufficient voltage to the power supply
Normal Condition
Damage to SPD1
Damage to SPD2
Installation instructions for
SPC Max Series surge protective device
Solution
N/A
N/A
Replace SPD
a
Check electrical system for TOV sources, correct, replace SPD
Replace SPD
a
Replace SPD
a
Replace SPD
a
Replace SPD
a
Replace SPD with correct voltage model
Check electrical system for TOV sources, correct, replace SPD
Replace SPD
a
Normal operation
If power is cycled and a fault condition still exists, the Audible
Alarm will reactivate
Check system voltage at SPD connection
Check SPD connections
Verify ribbon cable and connector are properly
aligned and fully seated together
Replace SPD
No Action
Replace SPD1
Replace SPD2
Check 10 pin ribbon cables to see if they are plugged in correctly
with the key oriented in the proper direction on top of each SPD
a
a