Installation instructions for
SPC Max Series surge protective device
To the right of Timezone, select the appropriate timezone from
the dropdown list . GMT-05:00 represents Eastern Standard Time,
GMT-06:00 represents Central Time, etc .; Date Format, with four
different date formats to choose from; and the Time Format .
Figure 40. Select time format
Device Actions has two options for the Admin user: Reboot or
Reset Device . Reboot is a soft reset; the microcontroller will power
down and power up . Reset is a hard reset that will reset the device
to factory defaults . Either action can only be conducted by an
Admin User .
Figure 41. Device actions
The user will be prompted before either of these actions . Click the X
in the top right of the window to cancel this action .
Figure 42. Reboot device alert
Instruction Booklet IB158002EN
The Admin User can modify timeouts, number of concurrent
sessions, and the number of failed login attempts .
Figure 43. Modifying timeouts
In the Network window, the following options are listed .
Figure 44. Network tab options
The user can select the IP allocation method between three options
and the IP address is also displayed here . The IP allocation method
change does not take effect until the unit has been rebooted . The
reboot command is available under General tab, Device Actions .
(Do not select the Factory Reset command or the device will return
to the factory default value with a static IP address .)
IP Allocation Methods available:
Statically Hardcoded (192 .168 .1 .254) Factory default
DHCP Allocated (Network assigned)
Taken from NV (stored IP address)
N
ote:
The user must reboot the device after performing any of
these changes .
Effective September 2023
EATON www.eaton.com
17