SPDV60-300
(Single mode, 220-250V (380-440V), 60/30kA)
FEATURES
•
1 mode plug-in protection (L-N)
•
Compact solution for primary protection
•
DIN43880 base, 35 mm DIN-rail mountable
•
MOV is thermally protected
•
Includes dry-contact alarm
Applications
•
Mains point-of-entry /Main SWB
•
Telecommunication Systems / Rectifiers
•
Process and Control Systems / Factories & Units
•
Computer Systems / Medical Systems
•
All sensitive Electronic Equipment
SPECIFICATIONS
Manufacturers name and model
Method of mounting
Input voltage
Maximum continuous operating
voltage - MCOV
Service type
Test classification
Supply current
Initial clamp voltage
Maximum rated surge current -
Ismax 8/20us
Nominal surge current - In
8/20us
Residual voltage (Vpl) @
3kA, 8/20uS
Residual voltage (Vpl) @ Ismax
30kA, 8/20uS
Energy absorbtion (2ms)
Nominal surge lifetime (In)
Internal protection
External disconnector
requirements
Terminations
Alarms/indicators
Location Category
Enclosure rating
Applicable standards.
Dimensions
Weight
Environment
Warranty
Specification are subject to change without notice. Copyright 2007 Eaton Power Quality Pty Ltd
S
D
URGE
IVERTER
Eaton Powerware
SPDV60-300
Fixed. DIN Rail mount
220-250VAC (380-440V)
40-70Hz
300VAC
TN-C and TN C-S (3-phase
with grounded neutral)
Class II
<10mA
470V
60kA
30kA
1.0kV
1.4kV
2130j
30kA (8/20uS), 20 times
MOV thermal disconnect
device
Gg/Gl HRC fuses, 1 per
unit/phase, 160A maximum.
2
Power terminals 25mm
2
Alarm terminals 1.5mm
Flag indicator, dry contact
alarm relay –
250VAC/24VDC, 2A
Indoor
IP20
IEC61643-1, IEC610006,
ANSI/IEEE C62.41,
AS1768-1991, AS3100
DIN43880, 1 units (17mm)
100g
-10 to 60C, 0-90%RH
12 months, workmanship
and materials
Technical Specification –SPDV60-300
Web:
http://www.powerware.com.au
FUNCTIONAL DESCRIPTION
The SPDV60-300 is designed to protect single and 3-
phase power systems against damage from surges
and spikes caused by lightning and other electrical
sources. The unit is intended for point-of-entry or
sub-board protection and is connected in parallel with
the power system via HRC fuses. The unit features a
plug-in module that may be replaced without rewiring
in the event of a fault. Check that the model you have
purchased is rated correctly for your power system.
.
This model (SPDV60-300) is designed for single
and 3-phase power systems, with a grounded
neutral, in the range of 220-250V(380-440V). If
your power system is "delta" (i.e. ungrounded),
or a different voltage, this model is NOT suitable.
Please contact your supplier for a suitable model to
suit your application.
OPERATION
The operational status of the unit is shown by a flag
indicator on the front of the module. In normal
operation, the flag is green. If the unit becaomes
damaged, the flag changes to red, indicating that
replacement is necessary. A 'dry-contact' alarm
output is fitted to the base unit and will change over if
the module is faulty or not in place.
WARRANTY
Eaton Power Quality warrants this unit against faulty
parts and workmanship for a period of 12 months
from the date of purchase. If this product fails to
operate correctly, please contact your Eaton
representative. This warranty doesn't cover neglect
or intentional misuse. As this product is intended for
use in electrically harsh environments no claim is
made of suitability for purpose. This unit is designed
to reduce the likelihood of damage, not prevent it.
Please also note that an excessive surge, such as
from a direct lightning strike to the site or a power
,
system fault, may cause damage to the unit and
render it inoperable. A unit that has been damaged in
this way is not warrantable.
Page 1 of 2