Troubleshooting The Power Xpert Spd - Eaton SPC Max Series Installation Instructions Manual

Surge protective device
Hide thumbs Also See for SPC Max Series:
Table of Contents

Advertisement

Installation instructions for
SPC Max Series surge protective device

Troubleshooting the Power Xpert SPD

Many SPD failures result from improper installation . Once the
Power Xpert SPD is installed properly, it is a highly reliable unit .
If the SPD does not function properly, first confirm that it is installed
properly . See Installation on page 3 .
If the SPD malfunctions after it has been operating routinely, refer
to Table 6 . This troubleshooting chart identifies possible causes
and solutions to the malfunction . Further assistance may be
obtained by calling Eaton's application engineers at 1-800-809-2772
or email SPD@eaton.com, including being directed to the warranty
process if applicable .
Table 6. Troubleshooting chart for Power Xpert SPD
Condition
Phase LEDs are green (1 per phase) and neu/gnd LED is green.
Audible alarm OFF, Form C (NC) contact in the CLOSED state
One phase LED is red, audible alarm is ON
NEU/GND LED is red, audible alarm is ON (for models
with neutral connections)
All phase LEDs are red, audible alarm is ON
One of the display LEDs is red, audible alarm is OFF
All LEDs are OFF, LCD display is OFF
One or more phase LED is yellow and NEU/GND LED is green
Surge counts are accumulating rapidly
Stuck button error on the local display
LCD is turning off/on and there is no communication
Error "Web page not working"
BACnet port not communicating
Modbus port not communicating
Webpage not secure notice
Web UI surge and general logs will not load
Time stamps inaccurate
Any LCD communication setting 'save' initiates a soft reset
Probable cause
Normal operation
Normal operation
Phase protection compromised or lost
Extended temporary overvoltage (TOV)
Significant surge event
NEU/GND protection is compromised or lost
Significant surge event
All phase protection has been lost
SPD rated voltage is less than system voltage
Extended temporary overvoltage (TOV)
Significant surge event
Audible alarm silence button has been depressed and
Alarm is silenced
SPD is not connected to a power source
SPD has lost some protection on the phase with the yellow LED
Noise on phase line
One or more of the buttons were depressing during startup
Insufficient input voltage
Available TCP connection limit reached
BACnet setting disabled (default)
Modbus setting disabled (default)
Security certificate not installed
Modbus disabled
Clock not synced
Supercap drained of power during extended power loss
All communication settings modifications require
reboot to enable
Instruction Booklet IB158002EN
Effective September 2023
Solution
N/A
N/A
Replace SPD
Check electrical system for TOV sources, correct, replace SPD
Replace SPD
Replace SPD
Replace SPD
Replace SPD
Replace SPD with correct voltage model.
Check electrical system for TOV sources, correct, replace SPD
Replace SPD
Normal operation
If power is cycled and a fault condition still exists, the audible
alarm will reactivate, replace SPD
Check system voltage at SPD connection
Check SPD connections
Monitor SPD, some protection has been lost
Contact the Eaton Technical Resource Center at 1-800-809-2772
or email SPD@eaton.com
Clear buttons of any obstructions; if that doesn't resolve
the matter, contact the Eaton Technical Resource Center at
1-800-809-2772 or email SPD@eaton.com
Verify phase voltages are within tolerances
Close excess webpage tabs or applications attempting
to access port
Enable BACnet and reboot device
Enable Modbus and reboot device
Download and install certificate
Enable Modbus and reboot device
Set clock and use SNTP feature to maintain accurate time stamp
Must re-enter settings menu each time a communication
setting is changed
EATON www.eaton.com
21