Power Xpert SPD Modbus register map, continued
Register
Name
11500
Indicates the status of Phase A Green
LED
11501
Indicates the status of Phase A Yellow
LED
11502
Indicates the status of Phase A Red LED BOOL RO
11503
Indicates the status of Phase B Green
LED
11504
Indicates the status of Phase B Yellow
LED
11505
Indicates the status of Phase B Red LED BOOL RO
11506
Indicates the status of Phase C Green
LED
11507
Indicates the status of Phase C Yellow
LED
11508
Indicates the status of Phase C Red LED BOOL RO
11509
Alarm status
11510
Percentage of protection on N-G
11511
Percentage of protection on Phase A
11512
Percentage of protection on Phase B
11513
Percentage of protection on Phase C
11514
Silences the Alarm. Setting the value,
will silence the Alarm
11515
Ambient temperature of SPD device
11517
General log Indicator
11767
General log Timestamp
12267
General log Index
Attributes
BOOL RO
Default: 0
BOOL RO
Default: 0
Default: 0
BOOL RO
Default: 0
BOOL RO
Default: 0
Default: 0
BOOL RO
Default: 0
BOOL RO
Default: 0
Default: 0
UINT8 RO
Default: 0
Enum
UINT16 RO
Default: 0
UINT16 RO
Default: 0
UINT16 RO
Default: 0
UINT16 RO
Default: 0
BOOL RW
Default: 0
FLOAT RO
Default: 0
UINT16 RO
Array size: 250
Default: 0
Enum
UINT32 RO
Array size: 250
Default: 0
UINT16 RO
Default: 0
Range: 0 to 250
Description
Indicates the status of phase-A green LED, 0:Led off 1:LED on. Indicates protection status on phase-A
Indicates the status of phase-A yellow LED, 0:LED off 1:LED on. Indicates protection status on phase-A
Indicates the status of phase-A red LED, 0:LED off 1:LED on. Indicates protection status on phase-A
Indicates the status of phase-B green LED, 0:LED off 1:LED on. Indicates protection status on phase-B
Indicates the status of phase-B yellow LED, 0:LED off 1:LED on. Indicates protection status on phase-B
Indicates the status of phase-B red LED, 0:LED off 1:LED on. Indicates protection status on phase-B
Indicates the status of phase-C green LED, 0:LED off 1:LED on. Indicates protection status on phase-C
Indicates the status of phase-C yellow LED, 0:LED off 1:LED on. Indicates protection status on phase-C
Indicates the status of phase-C red LED, 0:LED off 1:LED on. Indicates protection status on phase-C
Power Xpert SPD alarm status, alarm is used to indicate protection status
Value
Description
0
Alarm OFF
1
Alarm ON
Percentage of protection available on NG
Percentage of protection available on phase A
Percentage of protection available on phase B
Percentage of protection available on phase C
Silences the Alarm. Setting the value will silence the alarm.
Ambient temperature in Celsius
General log Indicator
Value
Description
0
No event occurred
1
Protection reduced on phase A
2
Protection reduced on phase B
3
Protection reduced on phase C
4
Protection reduced on neutral ground
5
Protection loss on phase A
6
Protection loss on phase B
7
Protection loss on phase C
8
Protection loss on phase neutral ground
9
Alarm silenced
10
SPD powered off
11
SPD powered on
Stores the time stamp of general log events. Time stamp will be stored in epoch time.
Time stamp can be verified using register 123.
Array of 500 registers
Index points to the latest general event log