Ac Input Wires; Terra 94; Terra 104 - ABB InCharge Terra 184 Manual

All-in-one 90kw dc fast charger
Hide thumbs Also See for InCharge Terra 184:
Table of Contents

Advertisement

Parameter
Input voltage A
Input voltage B
The EVSE must be wired with a WYE input, as shown in the diagram. Do not connect
a neutral wire to the EVSE.
10.16.2

AC input wires

Parameter
Wire shielding (optional)
Diameter of the phase conductors
Diameter of the PE conductor
Surface and diameter
Material
Maximum temperature of the input
wires
Diameter of each AC wire, including
shielding
10.16.3

Terra 94

Parameter
Maximum rated input current
Recommended input circuit breaker
Maximum power dissipation
Short circuit current rating
Maximum size of the input wire
10.16.4

Terra 104

Parameter
Maximum rated input current
Recommended input circuit breaker
Maximum power dissipation
Short circuit current rating
Maximum size of the input wire
9AKK108466A3703-EN | 001
Note: Power limiting is possible via software configuration.
Specification
480 V
277 V
Specification
If the local rules require shielded wires,
connect the wire shielding to the PE rail
at both ends of the wire.
Refer to the local rules.
Refer to the local rules
Based on current rating of the EVSE and
local regulations
Copper and aluminium
75 °C (167 °F)
34 to 45 mm (1.3 - 1.8 in)
Specification
115 A
150 A
95.7 kVA
65 kA
500 kcmil
Specification
130 A
175 A
106.3 kVA
65 kA
500 kcmil
Technical data
95

Advertisement

Table of Contents
loading

Table of Contents