Figure 3-34 Connecting cables for combined cabinets
----End

3.2.2.2 Installing the UPS on Channel Steel

● The Company does not provide channel steel or expansion bolts used for
● Ensure that the spacing between external sides of a channel steel is 800 mm.
● Keep the channel steel surface flat.
Step 1 Determine the cabinet installation positions on the channel steel based on holes in
the marking-off template for channel steel installation.
Issue 17 (2023-07-10)
NO TICE
securing channel steel. It is recommended that the customer purchase at least
50 mm wide channel steel.
Secure channel steel to the ground by using expansion bolts.
NO TE
● A: mounting holes on the channel steel
● B: mounting holes on the floor
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Installation
100