3.2.1.2 Installing the UPS on Channel Steel

Context
● The Company does not provide channel steel or expansion bolts used for
● Ensure that the spacing between external sides of a channel steel is 800 mm.
● Cabinet mounting holes must be aligned with channel steel mounting holes,
● Keep the channel steel surface flat.
Procedure
Step 1 Determine the cabinet installation positions on the channel steel based on holes in
the marking-off template for channel steel installation.
Figure 3-21 Mounting hole dimensions for the 400 kVA UPS and 500 kVA UPS
(unit: mm)
Issue 17 (2023-07-10)
NO TICE
securing channel steel. It is recommended that the customer purchase at least
50 mm wide channel steel.
Secure channel steel to the ground by using expansion bolts.
and secure the cabinet to channel steel with bolts.
NO TE
● A: mounting holes on the channel steel
● B: mounting holes on the floor
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Installation
89